← All methods

Volumetric flow rate from mass flow rate (smoke exhaust)

cibse_guide_e_chapter_10_equation_10_3

Calculates the volumetric flow rate for a smoke exhaust if the mass flow rate is known and, considering temperature dependence of density

Equations

V = \frac{m \cdot T_{s}}{\rho_{0} \cdot T_{0}}

Inputs